What is the difference between fire insulation and fire integrity?

Passive fire protection is a critical element of a building’s design. When properly implemented, it prevents the spread of fire throughout a building, a concept known as fire compartmentation. However, it’s important to note that this is only effective if the service penetration sealing is prioritised during the project’s design stage. This ensures that all firestopping requirements are considered, guaranteeing the correct products are installed in line with primary test evidence and manufacturers’ guidance. 

Test evidence is the key here. Without it, there is no assurance that products will perform as intended in the event of a fire, thus risking both life and building safety. This is why fire testing is not just crucial, but a responsibility that manufacturers and stakeholders must prioritise to ensure the use of tested firestopping solutions. 

Service penetrations are tested to the BS EN 1366-3 fire-resistance test standard. This measures the effectiveness of products in sealing openings created by services through fire-rated floors and walls. 

Fire testing is a challenging feat. It involves ample preparation, time, and resources. Once the specimen is ready to test, it is not as simple as exposing it to fire. Many factors work to determine the success of the test, including the concepts of insulation and integrity

These terms are frequently used in the construction industry, so understanding their roles is essential.

Insulation (I) measures a component’s time to resist a fire’s heat passing through to the non-fire side. This is to maintain the building’s compartmentation. The standard requires that the maximum temperature rise should not exceed 180°C above ambient. Insulation failure occurs at the same time integrity fails, as detailed in BS EN 1363-1:2020.

Furthermore, integrity (E) refers to the component’s ability to withstand fire and, like insulation, works to maintain the compartmentation. This is assessed using the ‘cotton pad’ test, which ensures that products retain their separating function without allowing a gap gauge, causing ignition of the cotton pad when applied as per BS EN 1363-1:2020, or resulting in sustained flaming on the unexposed surface.

Insulation and integrity are key indicators of an application’s performance in a fire scenario. When selecting the appropriate tested detail for a specific application, it’s important to consider the EI rating to ensure effective compartmentation. For instance, if your project requires an EI 120 rating, you should not select a tested detail with a rating below this. 

If you have any further questions, please don’t hesitate to contact us at technical@quelfire.co.uk.

Please Note

The information in this article was accurate at the time of publication. As the industry evolves, information may change too. Although we aim to keep our website updated, if it has been a significant amount of time since the publish date, please verify the information and contact us if you have any questions!

Alec Purdie, Technical, with a black-and-white filter. The background is an orange gradient.

This article was written by

Alec Purdie TIFireE

As Technical Manager at Quelfire, Alec Purdie leads the technical team in providing evidence-based guidance and support for firestopping solutions. A Technician member of the Institution of Fire Engineers (TIFireE), he combines recognised qualifications with industry experience to help clients design and deliver projects with tested, compliant details from the outset.

Leave a comment

Please note: comments must be approved before they are published.