Cast In Fire Collar | QuelCast

QuelCast CE Marked Cast In Fire Collars prevent the spread of fire through plastic pipes and cables where they penetrate concrete floors.

Features & Benefits

  • Up to 4 hour fire rating (EI240)
  • Fire resistance testing to BS EN 1366-3:2009
  • Suitable for PVC, PVC-U, PE, HDPE, MDPE, & PP pipes
  • Available to suit 50mm, 110mm & 160mm pipes
  • Performance unaffected by weathering (Type X Durability)
  • Quick & simple installation
  • Integrated moisture and smoke seal
  • Strong lid to carry foot traffic and light access equipment
  • No backfilling generally required
  • Compact footprint allows for closer positioning of pipes

Regulations

Building Regulations impose limitations on all pipes and cables passing through fire compartment floors. QuelCast CE Marked Cast In Fire Collars allow plastic pipes and cables to meet the requirements of the Building Regulations. QuelCast CE Marked Cast In Fire Collars have been tested according to BSEN 1366-3: 2009 where pipe diameters of up to 160mm have met insulation and integrity criteria for this standard for up to four hours.

Name: QuelCast Cast In Fire Collar

SKU: QUELCAST

Size:
Quantity:
View Product Downloads

Composition

QuelCast CE Marked Fire Collars are constructed from a robust polypropylene material and contain a high performance intumescent material which reacts under the influence of heat. This will exert pressure on the pipe as it softens, to form a carbonaceous char which provides an effective insulation plug thus preventing smoke and fire passing through to the adjoining compartment.

Standards & Approvals

  • Fire resistance testing to BS EN 1366-3:2009
  • EI60, EI120, EI180, EI240
  • Classified to EN 13501-2: 2007 + A1: 2009

Sample Specification

Install QuelCast CE Marked Cast In Fire Collars to provide up to 4 hours fire protection to maintain the fire rating of concrete floor slabs where plastic pipes and cables penetrate. Installation to be in accordance with manufacturer’s instructions.

Technical Support & Guidance

Should you require any further information regarding this product, please don’t hesitate to contact one of our specialists.

Application / installation


The QuelCast CE Marked Cast In Fire Collar has been designed at 250mm high to meet the requirements of most applications.

Simple installations steps:

  1. Mark the formwork with a cross where the pipe is to pass through the floor
  2. Position the QuelCast CE Marked Cast In Fire Collar as required (the centre line marks on the QuelCast Collars and Manifold help to position in the correct location)
  3. Attach to the formwork using screws or nails through the holes in the 4 corners of the unit
  4. Pour the concrete to the required depth
  5. On completion of concrete curing, remove all formwork and shuttering
  6. Remove the cap from the top of the QuelCast Collar
  7. Place the pipe through the QuelCast Collar

Additional instructions for QuelCast50:

For the QuelCast50 CE Marked Cast In Fire Collar, the space between the pipe and the outer casing of the QuelCast50 should be ‘backfilled’ with mineral wool from the rubber smoke seal to the top of the floor slab.


Contact us for Technical Advice

Applications where the floor slab depth is between 150 – 250mm

For applications where the floor slab depth is between 150 – 250mm cut the QuelCast CE Marked Fire Collar down to the required height and replace the cap. We also offer a pre-cut service so please contact Quelfire with your project requirements.

Cross-section of QuelCast CE Marked Cast In Fire Collar Cut to Suit a 150mm Floor Slab

Applications where the floor slab depth is greater than 250mm

For applications where the floor slab depth is greater than 250mm we manufacture an extension tube to suit the depth of the concrete slab. Please contact us to discuss your project requirements.

Cross-section of QuelCast110 CE Marked Cast In Fire Collar with and Extension Tube to Suit a Thicker Floor Slab

QuelCast Manifold

The QuelCast Manifold has been designed and developed to create a 75 mm recess in the floor slab either on the top or on the bottom of the floor slab to allow for applications for example:

  • Shower traps for walk-in showers and wet rooms
  • Soil pipe manifolds
  • Pipe connections
  • Limited ceiling space

 

Where there is limited ceiling space and so the plastic pipe can be installed closer to the ceiling with the pipe connection recessed in the slab.

When installing the QuelCast Manifold on the underside of the floor slab, ensure that you cut off the spigot on the manifold and then, using self-tapping steel screws, secure the QuelCast110 Cast In Fire Collar to the manifold.

When installing the Manifold on the top side of the floor slab, the Manifold spigot is simply slotted into the top of the QuelCast110 Cast In Fire Collar.

 

Performance

Product Code Description To suit Qty. Per Box Fire Rating
QUELCAST50 QuelCast50 Cast In Fire Collar to suit 50mm pipes 50mm dia. pipe 8 Up to 4 Hours
QUELCAST110 QuelCast110 Cast In Fire Collar to suit 110mm pipes 110mm dia. pipe 8 Up to 4 Hours
QUELCAST160 QuelCast160 Cast In Fire Collar to suit 160mm pipes 160mm dia. pipe 4 Up to 4 Hours
QUELCAST-MANIFOLD QuelCast Manifold Recess Former QUELCAST110 4 Up to 4 Hours*

*When used in conjunction with QuelCast110