QuelStop Fire Batt is used to maintain the fire integrity of compartment walls or floors, typically where oversized holes have been formed for services. A single or double batt may be required depending on a number of factors and it can also be fitted as a pattress fit (or face fit) too.
QuelStop Fire Batt is always installed in conjunction with QuelStop Intumescent Acrylic Sealant which is applied to all cuts, joints and exposed edges.
Where combustible, non-combustible services and insulated services penetrate the QuelStop Fire Batt seal the following additional products may be required:
- QuelCoil Intuwrap
- QWR Fire Collar
- QRS Fire Sleeve
- QuelStop HPE Graphite Sealant
- QuelStop Intumescent Acrylic Sealant
- QIF Insulated Fire Sleeve
- QI Intufoam
For full details on the size of seals, the spacing of services, batt overlap requirements, seal details etc refer to all available documentation, installation details and the Quelfire Technical team.
QuelStop Fire Batt can be installed in many different ways. In all cases the surfaces, letterbox and services must be clean of contaminants and dust free and the batt must be installed with QuelStop Intumescent Acrylic Sealant and in conjunction with the supporting documentation provided. To give some idea of the scope of the system, some indicative installation details are:
QuelStop Fire Batt in a letterbox opening with multiple services used in conjunction with other Quelfire products including QuelStop HPE Sealant and QRS Fire Sleeves
QuelStop Fire Batt as a pattress (or face fit) installation used in conjunction with other Quelfire products including QuelCoil Intuwrap to insulated non-combustible pipes.
View full installation instructions below:
*Please note that custom made items can expect to have longer lead times. Next working day is typical but can depend on outside factors not controlled by Quelfire.
Product Info & Features
Product Information
| Category | Details |
|---|---|
| Size | 1200mm x 600mm, 50mm thick, 140kg/m³ density |
| Packaging & Storage | QuelStop Fire Batt is supplied as a 1200x600mmx50mm slab, individually wrapped in polythene and is usually shipped on a pallet. It must be stored in dry conditions between +5°C and +40°C. |
| Health & Safety | QuelStop Fire Batt is manufactured from stone wool insulation which consists of small fibres. Appropriate protective clothing, including gloves, dust mask, safety glasses, should be worn, especially during cutting and installation, to guard against dust inhalation, eye, and skin irritation. |
Features & Benefits
-
Up to 2 hour fire rating
-
Suitable for use in flexible walls, rigid walls and floors
-
Suitable for use around cables, cable bunches, cable trays, cable ladders and non-combustible pipes
-
Also suitable for use around plastic pipes and insulated non-combustible pipes with the addition of other Quelfire products
-
Can be used as a blank seal as a head of wall detail
-
Can be installed into both lined and unlined apertures in partitions walls
-
Can be installed as a single or double batt seal
-
Can be pattress fitted / face fixed to walls
-
Tested with plasterboard ceilings and steel composite profile decks
-
Can be used in conjunction with Intufoam to allow for deflection head movement.
Product Information
| Category | Details |
|---|---|
| Size | 1200mm x 600mm, 50mm thick, 140kg/m³ density |
| Packaging & Storage | QuelStop Fire Batt is supplied as a 1200x600mmx50mm slab, individually wrapped in polythene and is usually shipped on a pallet. It must be stored in dry conditions between +5°C and +40°C. |
| Health & Safety | QuelStop Fire Batt is manufactured from stone wool insulation which consists of small fibres. Appropriate protective clothing, including gloves, dust mask, safety glasses, should be worn, especially during cutting and installation, to guard against dust inhalation, eye, and skin irritation. |
Features & Benefits
-
Up to 2 hour fire rating
-
Suitable for use in flexible walls, rigid walls and floors
-
Suitable for use around cables, cable bunches, cable trays, cable ladders and non-combustible pipes
-
Also suitable for use around plastic pipes and insulated non-combustible pipes with the addition of other Quelfire products
-
Can be used as a blank seal as a head of wall detail
-
Can be installed into both lined and unlined apertures in partitions walls
-
Can be installed as a single or double batt seal
-
Can be pattress fitted / face fixed to walls
-
Tested with plasterboard ceilings and steel composite profile decks
-
Can be used in conjunction with Intufoam to allow for deflection head movement.
Product Documentation
| File | |
|---|---|
| Product Data Sheet | Download |
| Installation Instructions | Download |
| Installation Instructions (Single Sided Access) | Download |
| Installation Instructions (Specwall) | Download |
| Material Safety Data Sheet (COSHH) | Download |
| Declaration of Performance | Download |
| Certificate of Constancy of Performance | Download |
Standard Installation Detail Examples
| File | |
|---|---|
| QB-CF150-D-00 | QuelStop Fire Batt Blank Seal for a Rigid Floor | View |
| QB-CF150-D-01 | Cable Penetrating a Rigid Floor | View |
| QB-CF150-D-06 | Plastic Pipe Penetrating a Rigid Floor | View |
| QB-CF150-D-10 | Metal Pipe Penetrating a Rigid Floor | View |
| QB-FW100-D-01 | Cable Penetrating a Flexible or Rigid Wall | View |
Browse More Tested Details
We have listed just five examples of tested details using QB50 Fire Batt though there are more available. In total, our standard installation details library contains over 600 tested details across our full product range.
Videos
Frequently Asked Questions
What is Fire Batt?
What is Fire Batt?
Fire Batt is a high-density mineral wool board, coated on one or both sides with a fire-resistant sealant, designed to reinstate fire resistance in wall and floor penetrations
How does Fire Batt work?
How does Fire Batt work?
The mineral wool core provides thermal and acoustic insulation, while the ablative coating reacts to fire, creating a robust barrier that prevents flames, smoke, and heat from spreading.
Can Fire Batt be cut to size on site?
Can Fire Batt be cut to size on site?
Yes – it can be cut using a sharp knife or saw to suit the required opening, making it flexible and adaptable for different service penetrations.
Do I need to use Fire Batt with other firestopping products?
Do I need to use Fire Batt with other firestopping products?
In many cases, yes. For example, service penetrations may also require wraps, collars, or sealants to ensure the full system is compliant with test evidence.
Does Fire Batt provide acoustic benefits as well?
Does Fire Batt provide acoustic benefits as well?
Yes – in addition to fire resistance, Fire Batt also offers sound insulation, helping to maintain acoustic performance across walls and floors.
How is Fire Batt fixed in place?
How is Fire Batt fixed in place?
It’s typically friction-fitted into the opening and sealed around the edges with the manufacturer’s approved fire-resistant mastic; in our case, that would be our QSS Acrylic Sealant.